Agency-wise Major/critical Ncs at OHT

S.No. Scheme ID Scheme Name OHT Code Non-Compliance Compliance(Current Status)
Description
Major Honey Comb Alignment Cube Test Exposure Deviation Tank Observation Other SBC Issue Demolish Partially Demolish Fully Under Examination Serious Observation Water Body Compliance Major Honey Comb Compliance Alignment Compliance Cube Test Compliance Exposure Compliance Deviation Compliance Tank Compliance Other Compliance SBC Issue Compliance Demolish Partially Compliance Demolish Fully Compliance Under Examination Compliance Serious Observation Compliance Water Body
1 20012442 Bhuwalpur Sisni GP Water Supply Scheme 20012442/01 No No No No Yes No No No No No No No No Lap provided in non-lapping Zone
2 20085623 Gora Ubarani Water Supply Scheme 20085623/01 No Yes No No No No No No No No No No No One or more RCC columns appear not vertically plumb when observed from the side angle
3 20090886 Kathgar Water Supply Scheme 20090886-OHT-01 No Yes No No No No No No No No No No No lt has been observed that the column above 3rd brace beams have undergone extensive repairs and are misaligned.
4 20012772 Jariya GP Water Supply Scheme 20012772-OHT-01 No Yes No No No No No No No No No No No lt has been observed through visual inspection that the one column above 1st and 2nd brace beams are misaligned,
5 20062178 JAHANPUR KODAR WATER SUPPLY SCHEME 20062178-OHT-01 No Yes No No No No No No No No No No No lt has been observed through visual inspection that the one column above 1st and 2nd brace beams are misaligned,
6 20094592 Lakhanpur Water Supply Scheme 20094592-OHT-01 No Yes No No No No No No No No No No No From visual inspection, the column appears to be misaligned. The change in its profile and the eccentricity near the beam connection suggest that the column may not be perfectly vertical or centered.
7 20090875 SAWANPUR NEWADA Water Supply Scheme 20090875-OHT-01 No Yes No No No No No No No No No No No From visual inspection, the column appears to be misaligned. The change in its profile and the eccentricity near the beam connection suggest that the column may not be perfectly vertical or centered.
8 8362069 JARIYARI 8362069-OHT-01 No Yes No No No No No No No No No No No From visual inspection, the column appears to be misaligned. The change in its profile and the eccentricity near the beam connection suggest that the column may not be perfectly vertical and Honeycombing also found in Ring beam and Column."
9 8362109 PAHARPUR KAHSO 8362109-OHT-01 No Yes No No No No No No No No No No No Column above TB2 and TB3 appears to be misaligned from visual inspection.
10 20064090 Khanuwa WATER SUPPLY SCHEME 20064090/01 No Yes No No No No No No No No No No No It was observed that 02 columns appear to be misaligned from the intended alignment. Futhermore, improper linishing was observed at the colurnn-beam junction.
11 20012459 Rampur Kasiha GP Water Supply Scheme 20012459/01 No Yes No No No No No No No No No No No From visual inspection, the column appears to be misaligned.
12 8362090 SARAIDAMU 8362090-OHT-01 No Yes No No No No No No No No No No No From visual inspection 2 columns appear to be misaligned from the intended alignment. Furthermore, improper finishing was observed at the column-beam junction.
13 8362072 SEMRA 8362072-OHT-01 Yes No No No No No No No No No No No No Resolved Honeycombing was repaired by applying Nitobond as a bonding agent, filling cavities with Conbextra GP2. 2.After proper curing, an Ultrasonic Pulse Velocity (UPV) test was conducted.
14 8362192 BAGHAIL 8362192-OHT-01 Yes No No No No No No No No No No No No Resolved • Honeycombing was repaired by applying Nitobond as a bonding agent, filling cavities with Conbextra GP2. • After proper curing, an Ultrasonic Pulse Velocity (UPV) test was conducted
15 20090255 BEWAL WATER SUPPLY 20090255/01 Yes No No No No No No No No No No No No Resolved • Honeycombing was repaired by applying Nitobond as a bonding agent, filling cavities with Conbextra GP2. • After proper curing, an Ultrasonic Pulse Velocity (UPV) test was conducted
16 20090251 BARARA BUJURG Water Supply Scheme 20090251-OHT-01 Yes No No No No No No No No No No No No Resolved • Honeycombing was repaired by applying Nitobond as a bonding agent, filling cavities with Conbextra GP2. • After proper curing, an Ultrasonic Pulse Velocity (UPV) test was conducted
17 8361895 SEONTHI 8361895-OHT-01 Yes No No No No No No No No No No No No Resolved Honeycombing was repaired by applying Nitobond as a bonding agent, filling cavities with Conbextra GP2. • After proper curing, an Ultrasonic Pulse Velocity (UPV) test was conducted
18 8388533 Jamuvava 8388533/01 Yes No No No No No No No No No No No No Resolved Honeycombing was repaired by applying Nitobond as a bonding agent, filling cavities with Conbextra GP2. • After proper curing, an Ultrasonic Pulse Velocity (UPV) test was conducted
19 20062204 ADILABAD WATER SUPPLY SCHEME 20062204/01 Yes No No No No No No No No No No No No Resolved Honeycombing was repaired by applying Nitobond as a bonding agent, filling cavities with Conbextra GP2. • After proper curing, an Ultrasonic Pulse Velocity (UPV) test was conducted.
20 20064074 Tanda WATER SUPPLY SCHEME 20064074-OHT-01 Yes No No No No No No No No No No No No Resolved Honeycombing was repaired by applying Nitobond as a bonding agent, filling cavities with Conbextra GP2. • After proper curing, an Ultrasonic Pulse Velocity (UPV) test was conducted.
21 20062206 SENDURA MAU WATER SUPPLY SCHEME 20062206/01 Yes No No No No No No No No No No No No Resolved Honeycombing was repaired by applying Nitobond as a bonding agent, filling cavities with Conbextra GP2. • After proper curing, an Ultrasonic Pulse Velocity (UPV) test was conducted.
22 8361878 AGHAURA 8361878-OHT-01 No No No No No Yes No No No No No No No Resolved The leakage observed in the Zinc–Alum water storage tanks has been successfully rectified. All seepage points were identified and repaired by tightening/replacing bolts, installing new neoprene/rubber washers, and applying food-grade internal sealant and external waterproof sealant to the affected joints. Stagnant water around the tank base was removed, the slab surface was cleaned and restored, and necessary waterproofing was carried out to prevent future seepage. After completion of the repair works, the tank was refilled and monitored for 24 hours. No leakage or seepage was observed during the testing period. The tank is now functioning normally, with proper water pressure restored to the distribution system.
23 20090632 BATHUWA KHAS Water Supply Scheme 20090632/01 No No No No No No Yes No No No No No No Resolved 1.The reinforcement bars were thoroughly cleaned using wire brushes to remove loose rust, scale, and foreign materials. 2.After proper surface preparation, Nito Zinc Primer was applied as per manufacturer’s specifications.
24 8361872 SARAI MUBARAK 8361872/01 No No No No No No Yes No No No No No No Resolved 1.The reinforcement bars were thoroughly cleaned using wire brushes to remove loose rust, scale, and foreign materials. 2.After proper surface preparation, Nito Zinc Primer was applied as per manufacturer’s specifications.
25 20062147 SONIKA MAU WATER SUPPLY SCHEME 20062147-OHT-01 No No No No No No Yes No No No No No No Resolved 1.The reinforcement bars were thoroughly cleaned using wire brushes to remove loose rust, scale, and foreign materials. 2.After proper surface preparation, Nito Zinc Primer was applied as per manufacturer’s specifications.
26 20090826 RAHWAN Water Supply Scheme 20090826-OHT-01 Yes No No No No No No No No No No No No Resolved 1. Honeycombing was repaired by applying Nitobond as a bonding agent, filling cavities with Conbextra GP2. 2.After proper curing, an Ultrasonic Pulse Velocity (UPV) test was conducted.
27 20089929 Dalmau Water Supply Scheme 20089929-OHT-01 Yes No No No No No No No No No No No No Resolved 1. Honeycombing was repaired by applying Nitobond as a bonding agent, filling cavities with Conbextra GP2. 2.After proper curing, an Ultrasonic Pulse Velocity (UPV) test was conducted.
28 8360965 Chandauli 8360965/01 No No No No No No Yes No No No No No No Resolved 1.The reinforcement bars were thoroughly cleaned using wire brushes to remove loose rust, scale, and foreign materials. 2.After proper surface preparation, Nito Zinc Primer was applied as per manufacturer’s specifications.
29 8362286 HIDAIN 8362286/01 No No No No No Yes No No No No No No No Resolved The leakage observed in the Zinc–Alum water storage tanks has been successfully rectified. All seepage points were identified and repaired by tightening/replacing bolts, installing new neoprene/rubber washers, and applying food-grade internal sealant and external waterproof sealant to the affected joints. Stagnant water around the tank base was removed, the slab surface was cleaned and restored, and necessary waterproofing was carried out to prevent future seepage. After completion of the repair works, the tank was refilled and monitored for 24 hours. No leakage or seepage was observed during the testing period. The tank is now functioning normally, with proper water pressure restored to the distribution system
30 20090029 Kamalpur Water Supply Scheme 20090029/01 Yes No No No No No No No No No No No No Resolved Honeycombing was repaired by applying Nitobond as a bonding agent, filling cavities with Conbextra GP2. 2.After proper curing, an Ultrasonic Pulse Velocity (UPV) test was conducted.
31 20014907 Maha Khera GP Water Supply Scheme 20014907/01 Yes No No No No No No No No No No No No Resolved 1.Honeycombing was repaired by applying Nitobond as a bonding agent, filling cavities with Conbextra GP2. 2.After proper curing, an Ultrasonic Pulse Velocity (UPV) test was conducted.
32 20062207 JHARAHA WATER SUPPLY SCHEME 20062207/01 Yes No No No No No No No No No No No No Resolved 1.Honeycombing was repaired by applying Nitobond as a bonding agent, filling cavities with Conbextra GP2. 2.After proper curing, an Ultrasonic Pulse Velocity (UPV) test was conducted.
33 8360623 Padri Ganeshpur 8360623-OHT-01 Yes No No No No No No No No No No No No Resolved Honeycombing was repaired by applying Nitobond as a bonding agent, filling cavities with Conbextra GP2. After proper curing, an Ultrasonic Pulse Velocity (UPV) test was conducted.
34 20064084 Baghai Ahalwar WATER SUPPLY SCHEME 20064084-OHT-01 Yes No No No No No No No No No No No No Resolved Honeycombing was repaired by applying Nitobond as a bonding agent, filling cavities with Conbextra GP2. After proper curing, an Ultrasonic Pulse Velocity (UPV) test was conducted.
35 8360622 Chandwal 8360622-OHT-01 Yes No No No No No No No No No No No No Resolved Honeycombing was repaired by applying Nitobond as a bonding agent, filling cavities with Conbextra GP2 .After proper curing, an Ultrasonic Pulse Velocity (UPV) test was conducted.
36 8362499 SULTANPUR 8362499/01 Yes No No No No No No No No No No No No Resolved Honeycombing was repaired by applying Nitobond as a bonding agent, filling cavities with Conbextra GP2.After proper curing, an Ultrasonic Pulse Velocity (UPV) test was conducted.
37 20017220 Baitu GP Water Supply Scheme 20017220-OHT-01 Yes No No No No No No No No No No No No Resolved Honeycombing was repaired by applying Nitobond as a bonding agent, filling cavities with Conbextra GP2. After proper curing, an Ultrasonic Pulse Velocity (UPV) test was conducted.
38 20022721 Ekauni GP Water Supply Scheme 20022721/01 No No No Yes No No No No No No No No No Resolved Rectification has been completed by removing loose concrete, cleaning the exposed reinforcement, applying anti-corrosion treatment/zinc-rich primer, and restoring the affected portion with suitable repair mortar. NDT testing has also been carried out after repair, and proper finishing and curing have been ensured.
39 20092516 Purasi Water Supply Scheme 20092516/01 Yes No No No No No No No No No No No No Resolved Honeycombing was repaired by applying Nitobond as a bonding agent, filling cavities with Conbextra GP2. After proper curing, an Ultrasonic Pulse Velocity (UPV) test was conducted.
40 8362389 KUNDAULI 8362389-OHT-01 Yes No No No No No No No No No No No No Resolved Honeycombing was repaired by applying Nitobond as a bonding agent, filling cavities with Conbextra GP2. After proper curing, an Ultrasonic Pulse Velocity (UPV) test was conducted.
41 20066102 Sarai Dugosha Water Supply Scheme 20066102-OHT-01 Yes No No No No No No No No No No No No Resolved Honeycombing was repaired by applying Nitobond as a bonding agent, filling cavities with Conbextra GP2. After proper curing, an Ultrasonic Pulse Velocity (UPV) test was conducted.
42 8362388 BANNAWA 8362388-OHT-01 No No No No No No Yes No No No No No No Resolved Poor finishing has been rectified and proper surface finishing has been achieved at the affected locations. Visible air voids have been repaired, and the embedded shuttering material at the slab bottom has been removed. Surface preparation and repainting have been carried out properly after rectification
43 20087184 Surasana Water Supply Scheme 20087184-OHT-01 No No No No No Yes No No No No No No No Resolved Liner of Zinc Alum Tank has been changed.
44 20062140 BADAWAR WATER SUPPLY SCHEME 20062140-OHT-01 Yes No No No No No No No No No No No No Resolved Honeycombing was repaired by applying Nitobond as a bonding agent, filling cavities with Conbextra GP2. 2.After proper curing, an Ultrasonic Pulse Velocity (UPV) test was conducted.
45 8362130 BAHUDA KHURD 8362130/01 Yes No No No No No No No No No No No No Resolved Honeycombing was repaired by applying Nitobond as a bonding agent, filling cavities with Conbextra GP2. 2.After proper curing, an Ultrasonic Pulse Velocity (UPV) test was conducted.
46 8360916 Jagjiwanpur Amariya 8360916/01 Yes No No No No No No No No No No No No Resolved Honeycombing was repaired by applying Nitobond as a bonding agent, filling cavities with Conbextra GP2. 2.After proper curing, an Ultrasonic Pulse Velocity (UPV) test was conducted
47 20012294 Kumbhi GP Water Supply Scheme 20012294-OHT-01 No No No Yes No No No No No No No No No Resolved 1.Rectification has been completed by removing loose concrete, cleaning the exposed reinforcement, applying anti-corrosion treatment/zinc-rich primer, and restoring the affected portion with suitable repair mortar. 2.NDT testing has also been carried out after repair, and proper finishing and curing have been ensured
48 20011312 Manehroo GP Water Supply Scheme 20011312-OHT-01 Yes No No No No No No No No No No No No Resolved Honeycombing was repaired by applying Nitobond as a bonding agent, filling cavities with Conbextra GP2. 2.After proper curing, an Ultrasonic Pulse Velocity (UPV) test was conducted.
49 20013146 Bisaiyya GP Water Supply Scheme 20013146/01 No No No Yes No No No No No No No No No Resolved Rectification has been completed by removing loose concrete, cleaning the exposed reinforcement, applying anti-corrosion treatment/zinc-rich primer, and restoring the affected portion with suitable repair mortar. NDT testing has also been carried out after repair, and proper finishing and curing have been ensured
50 20012584 Pindauli GP Water supply Scheme 20012584/01 No No No Yes No No No No No No No No No Resolved Rectification has been completed by removing loose concrete, cleaning the exposed reinforcement, applying anti-corrosion treatment/zinc-rich primer, and restoring the affected portion with suitable repair mortar. NDT testing has also been carried out after repair, and proper finishing and curing have been ensured