| S.No. | Scheme ID | Scheme Name | OHT Code | Non-Compliance | Compliance(Current Status) | Description
|
||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Major Honey Comb | Alignment | Cube Test | Exposure | Deviation | Tank Observation | Other | SBC Issue | Demolish Partially | Demolish Fully | Under Examination | Serious Observation | Water Body | Compliance Major Honey Comb | Compliance Alignment | Compliance Cube Test | Compliance Exposure | Compliance Deviation | Compliance Tank | Compliance Other | Compliance SBC Issue | Compliance Demolish Partially | Compliance Demolish Fully | Compliance Under Examination | Compliance Serious Observation | Compliance Water Body | |||||
| 1 | 20008769 | Oya Water Supply Scheme | 20008769/01 | No | No | Yes | No | No | No | No | No | No | No | No | Yes | No | Resolved | Resolved | Concrete compressive strength test for foundation raft has been failed for 28 days of said structure. | |||||||||||
| 2 | 20057407 | dandra water supply scheme | 20057407/01 | No | Yes | No | No | No | No | No | No | Yes | No | No | No | No | Resolved | Resolved | Work done without checking, alignment of brace and column steel is inaccurate also cover to reinforcement not available. | |||||||||||
| 3 | 20057288 | MOHAMMD NAGAR SULRA WATER SUPPLY SCHEME | 20057288/01 | No | No | No | No | No | No | Yes | No | No | No | No | Yes | No | Resolved | Resolved | Sub-standard work done at site, concreting work performed at site while there was heavy mud present on pcc surface. | |||||||||||
| 4 | 20092208 | ANUGUIYA & USHAITA WATER SUPPLY SCHEME | 20092208/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | To Complete reinforecemnt as per approved drawing and to correct shuttering work, also to replacce material. | ||||||||||||
| 5 | 20101125 | gangaura water supply scheme | 20101125/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | To Complete reinforecemnt as per approved drawing | ||||||||||||
| 6 | 20085741 | BADSHAHPUR WATER SUPPLY SCHEME | 20085741/01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | Resolved | Honeycombing In brace and columns | ||||||||||||
| 7 | 20008501 | Ujhauli Water Supply Scheme | 20008501/01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | Resolved | Honeycombing In wall | ||||||||||||
| 8 | 20057282 | IKRI BASIYANI WATER SUPPLY SCHEME | 20057282/01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | Resolved | Honeycombing at junction of brace and column | ||||||||||||
| 9 | 20085744 | MAMOORGANJ WATER SUPPLY SCHEME | 20085744/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | Less reinforcement in bracing, Poor Shuttering Work. | ||||||||||||
| 10 | 20073013 | DHAURERA WATER SUPPLY SCHEME | 20073013/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | Sub-standard Material, shuttering work and reinfocement. | ||||||||||||
| 11 | 20086307 | KANHA NAGLA WATER SUPPLY SCHEME | 20086307/01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | Resolved | Honeycombing In brace and columns | ||||||||||||
| 12 | 20094195 | LAHI FARIDPUR WATER SUPPLY SCHEME | 20094195/01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | Resolved | Honeycombing In brace and columns | ||||||||||||
| 13 | 20072798 | DHAMEI WATER SUPPLY SCHEM E | 20072798/01 | No | No | No | Yes | No | No | Yes | No | Yes | No | No | No | No | Resolved | Resolved | Resolved | Poor Concreting work in foundation | ||||||||||
| 14 | 20092270 | nadail water supply scheme | 20092270/01 | No | Yes | No | No | No | No | No | No | No | No | No | Yes | No | Resolved | Resolved | Misalignment in brace and columns | |||||||||||
| 15 | 20065996 | Ranet Govindpur water supply scheme | 20065996/01 | Yes | No | No | Yes | No | No | No | No | Yes | No | No | No | No | Resolved | Resolved | Resolved | HoneyCombing in Column | ||||||||||
| 16 | 20073126 | papgaon water supply scheme | 20073126/01 | No | Yes | No | No | No | No | No | No | Yes | No | No | No | No | Resolved | Resolved | Misalignment | |||||||||||
| 17 | 20024358 | badnaumi | 20024358/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | Sub-standard material and rusted steel | ||||||||||||
| 18 | 20085889 | JATKI & SHMASPUR KUNVARI WATER SUPPLY SCHEME | 20085889/01 | No | No | No | Yes | No | No | Yes | No | No | No | No | Yes | No | Resolved | Resolved | Resolved | Substandard quality work at site | ||||||||||
| 19 | 20099115 | nagaria chikan water supply scheme | 20099115/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | Observations related to reinforcement | ||||||||||||
| 20 | 20072949 | RUKAMPUR PUKHTA & AMROLI WATER SUPPLY SCHEME | 20072949/01 | No | Yes | No | No | No | No | No | No | Yes | No | No | No | No | Resolved | Resolved | Column out of plumb | |||||||||||
| 21 | 20012272 | Changasi Water supply scheme | 20012272/01 | Yes | No | No | Yes | No | No | No | No | No | No | No | No | No | Resolved | Resolved | Exposure of reinforcment in bottom dome, minor cracks visible in bottom dome | |||||||||||
| 22 | 20072820 | BABEPUR & ZIZAMUDDINPUR SHAH WATER SUPPLY SCHEME | 20072820/01 | Yes | No | No | No | No | No | No | No | Yes | No | No | No | No | Resolved | Resolved | Honeycombing in Column | |||||||||||
| 23 | 20065957 | Kishanpur&Bhur Bisauli water supply scheme | 20065957/01 | Yes | No | No | No | No | No | No | No | Yes | No | No | No | No | Resolved | Resolved | Honeycombing In brace and columns | |||||||||||
| 24 | 20066001 | Dharampur biharipur& Manakpur water supply scheme | 20066001/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | Observations related to reinforcement | ||||||||||||
| 25 | 20008258 | Dahemu Water Supply Scheme | 20008258/01 | Yes | Yes | No | No | No | No | No | No | Yes | No | No | No | No | Resolved | Resolved | Resolved | Honeycombing and misalignment In brace and columns | ||||||||||
| 26 | 20008440 | Pipraul Pukhta Water Supply Scheme | 20008440/01 | Yes | Yes | No | No | No | No | No | No | Yes | No | No | No | No | Resolved | Resolved | Resolved | Honeycombing and misalignment In brace and columns | ||||||||||
| 27 | 20068295 | CHINJARI & KISHNI MAHERA WATER SUPPLY SCHEME | 20068295/01 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | Situated Near Ganga River, water logging in rainy days. (SBC-12.78T/M2 @ 2 MTR) | |||||||||||||
| 28 | 20085753 | KESHAUNPUR KALA WATER SUPPLY SCHEME | 20085753/01 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | OHT situated in village Pond, work is stopped from last 2 years. | |||||||||||||
| 29 | 20092205 | NANAKHERA PUKHTA WATER SUPPLY SCHEME | 20092205/01 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | NEAR GANGA RIVER, WATER LOGGING IN RAINY SEASON. (SBC-14.4T/M2 @ 2MTR) | |||||||||||||
| 30 | 8389902 | KHAJURARA PUKHTA | 8389902/01 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | NEAR GANGA RIVER, WATER LOGGING IN RAINY SEASON. (SBC- 11.22T/M2 @ 2MTR) | |||||||||||||
| 31 | 20056751 | tikra baccheli water supply scheme | 20056751/01 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | NEAR GANGA RIVER, WATER LOGGING IN RAINY DAYS. (SBC-13.77 T/M2 @ 2MTR) | |||||||||||||
| 32 | 20094104 | BHUDI WATER SUPPLY SCHEME | 20094104/01 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | NEAR GANGA RIVER, WATER LOGGING IN RAINY SEASON.(SBC-9.57 T/M2 @ 2MTR) | |||||||||||||
| 33 | 20008033 | Jaitpur Pukhta Water Supply Scheme | 20008033/01 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | NEAR GANGA RIVER, WATER LOGGING IN RAINY SEASON. (8.62T/M2 @ 2MTR) | |||||||||||||
| 34 | 20068009 | Garhia gangwarar water supply scheme | 20068009/01 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | NEAR GANGA RIVER, WATER LOGGING IN RAINY SEASON. (10.14 T/M2 @ 2MTR) | |||||||||||||
| 35 | 20081081 | majra gangwarara water supply scheme | 20081081/01 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | NEAR GANGA RIVER, WATER LOGGING IN RAINY SEASON. (SBC-16.4T/M2 @ 2MTR) | |||||||||||||
| 36 | 20092240 | TOTPUR KARSARI WATER SUPPLY SCHEME | 20092240/01 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | NEAR GANGA RIVER, WATER LOGGING IN RAINY SEASON. (SBC-18.2 T/M2 @ 2MTR) | |||||||||||||
| 37 | 20037242 | BAIRPUR WATER SUPPLY SCHEME | 20037242/01 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | NEAR GANGA RIVER, WATER LOGGING IN RAINY SEASON. (SBC-10.52 T/M2 @ 2MTR) | |||||||||||||
| 38 | 20092265 | bhawanipur khalli water supply scheme | 20092265/01 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | NEAR GANGA RIVER, WATER LOGGING IN RAINY SEASON. (SBC-09.74 T/M2 @ 2MTR) | |||||||||||||
| 39 | 20093958 | LOTHER & MAHANAGAR WATER SUPPLY SCHEME | 20093958/01 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | NEAR GANGA RIVER, WATER LOGGING IN RAINY SEASON. (SBC-27.10 T/M2 @ 2MTR) | |||||||||||||
| 40 | 20068300 | ABBU NAGAR & SHUJATGANJ BELA | 20068300/01 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | NEAR GANGA RIVER, WATER LOGGING IN RAINY SEASON. (SBC-20.40 T/M2 @ 2MTR) | |||||||||||||
| 41 | 20101126 | jiroli water supply scheme | 20101126/01 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | NEAR VILLAGE NALLAH, WATER LOGGING IN RAINY SEASON. (SBC-8.26 T/M2 @ 2MTR) | |||||||||||||
| 42 | 20081148 | HUSSAINPUR PUKHTA WATER SUPPLY SCHEME | 20081148/01 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | NEAR GANGA RIVER, WATER LOGGING IN RAINY SEASON. (SBC-26.70 T/M2 @ 2MTR) | |||||||||||||
| 43 | 20067093 | MUDA PUKHTA WATER SUPPLY SCHEME | 20067093/01 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | Resolved | NEAR GANGA RIVER, WATER LOGGING IN RAINY SEASON. (SBC-11.70 T/M2 @ 2MTR) Note: - Pile foundation recommanded in new SBC report. | ||||||||||||
| 44 | 20068624 | Nagala kotar water supply scheme | 20068624/01 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | Resolved | NEAR GANGA RIVER, WATER LOGGING IN RAINY SEASON. (SBC-12.62 T/M2 @ 2MTR) Note: - Pile foundation recommanded in new SBC report. | ||||||||||||
| 45 | 20009118 | Kharkwari Manpur Pukhta Water Supply Scheme | 20009118/01 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | Resolved | NEAR GANGA RIVER, WATER LOGGING IN RAINY SEASON. (SBC-18.96T/M2 @ 2MTR) Note: - Pile foundation recommanded in new SBC report. | ||||||||||||
| 46 | 20067439 | sithaulia pukhta water supply scheme | 20067439/01 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | Resolved | NEAR GANGA RIVER, WATER LOGGING IN RAINY SEASON. (SBC-14.50 T/M2 @ 2MTR) Note: - Pile foundation recommanded in new SBC report. | ||||||||||||
| 47 | 20008053 | Nagla Baran Water Supply Scheme | 20008053/01 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | Resolved | NEAR GANGA RIVER, WATER LOGGING IN RAINY SEASON. (SBC-9.11 T/M2 @ 2MTR) Note: - Pile foundation recommanded in new SBC report. | ||||||||||||
| 48 | 20068278 | Kasba Bhagta Nagla & Shahpur Tahirpu Khera | 20068278/01 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | Resolved | NEAR GANGA RIVER, WATER LOGGING IN RAINY SEASON. (SBC-12.50 T/M2 @ 2MTR) Note: - Pile foundation recommanded in new SBC report. | ||||||||||||
| 49 | 20085859 | NADHA WATER SUPPLY SCHEME | 20085859/01 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | Resolved | NEAR GANGA RIVER, WATER LOGGING IN RAINY SEASON. (SBC-9.75 T/M2 @ 2MTR) Note: - Pile foundation recommanded in new SBC report. | ||||||||||||
| 50 | 20094130 | DANPUR WATER SUPPLY SCHEME | 20094130/01 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | Resolved | NEAR GANGA RIVER, WATER LOGGING IN RAINY SEASON. (SBC-16.33 T/M2 @ 2MTR) Note: - Pile foundation recommanded in new SBC report. | ||||||||||||
| 51 | 20101378 | indrai water supply scheme | 20101378/01 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | Resolved | NEAR GANGA RIVER, WATER LOGGING IN RAINY SEASON. (SBC-9.45 T/M2 @ 2MTR) Note: - Pile foundation recommanded in new SBC report. | ||||||||||||
| 52 | 20037376 | CHANDANPUR PHUKTA WATER SUPPLY SCHEME | 20037376/01 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | Resolved | NEAR GANGA RIVER, WATER LOGGING IN RAINY SEASON. (SBC-11.22 T/M2 @ 2MTR) Note: - Pile foundation recommanded in new SBC report. | ||||||||||||
| 53 | 20068454 | Rampur khurd & Navada Madhukar water supply scheme | 20068454/01 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | Resolved | NEAR GANGA RIVER, WATER LOGGING IN RAINY SEASON. (SBC-8.22 T/M2 @ 2MTR) Note: - Pile foundation recommanded in new SBC report. | ||||||||||||
| 54 | 20068483 | Karanpur Pukhta & Vela Dandi Water Supply Scheme | 20068483/01 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | Resolved | NEAR GANGA RIVER, WATER LOGGING IN RAINY SEASON. (SBC-8.81 T/M2 @ 2MTR) Note: - Pile foundation recommand in new SBC report. | ||||||||||||
| 55 | 20008596 | Dayohara Shekhpur Water Supply Scheme | 20008596/01 | No | No | No | No | No | No | No | No | No | No | No | No | Yes | Resolved | NEAR GANGA RIVER, WATER LOGGING IN RAINY SEASON. (SBC-10.52 T/M2 @ 2MTR) Note: - Pile foundation recommanded in new SBC report. | ||||||||||||