| S.No. | Scheme ID | Scheme Name | OHT Code | Non-Compliance | Compliance(Current Status) | Description
|
||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Major Honey Comb | Alignment | Cube Test | Exposure | Deviation | Tank Observation | Other | SBC Issue | Demolish Partially | Demolish Fully | Under Examination | Serious Observation | Water Body | Compliance Major Honey Comb | Compliance Alignment | Compliance Cube Test | Compliance Exposure | Compliance Deviation | Compliance Tank | Compliance Other | Compliance SBC Issue | Compliance Demolish Partially | Compliance Demolish Fully | Compliance Under Examination | Compliance Serious Observation | Compliance Water Body | |||||
| 1 | 20014105 | KHUTENA PAYAGPUR PWS | 20014105/01 | Yes | No | No | No | No | No | Yes | No | No | No | No | No | No | *Improper overlapping of rebars. *Incorrect placement of chair bars. *Inadequate anchoring of bars and required adjustments in the formwork. *Major honeycombing observed in beams and pile cap due to improper use of shuttering & poor quality execution | |||||||||||||
| 2 | 8362923 | SIRAULA GRAM PANCHAYAT RURAL DRINKING WATER SUPPLY SCHEME | 8362923/01 | Yes | Yes | No | No | No | No | No | No | No | No | No | No | No | *Honeycomb seams in brace beam of OHT. *alignment issues and finishing issues in staircase. | |||||||||||||
| 3 | 20014710 | ALI NAGAR KHURD RISIYA MVS PWS | 20014710/01 | No | No | No | No | Yes | No | No | No | No | No | No | No | No | *Air voids and honeycomb in bottom ring beam of OHT. | |||||||||||||
| 4 | 20013696 | KAANDH BHARI VISESHWARGANJ PWS | 20013696/01 | Yes | Yes | No | No | No | No | No | No | No | No | No | No | No | *Minor honeycomb in 3rd brace beam. * Verticality issue in column. | |||||||||||||
| 5 | 20016690 | SALARPUR KAISARGANJ MVS PWS | 20016690/01 | Yes | No | No | No | Yes | No | No | No | No | No | No | No | No | *honeycomb and reinforcement issue in OHt bottom dome. * staircase waist slab thickness is not as per approved drawing . | |||||||||||||
| 6 | 20039628 | BASANTPUR HUZOORPUR PWS | 20039628/01 | Yes | No | No | No | Yes | No | No | No | No | No | No | No | No | *honeycomb in OHt bottom dome staircase waist slab . *stair caser work is not done as approved drawing. | |||||||||||||
| 7 | 20016681 | KHAJURA VISESHWARGANJ PWS | 20016681/01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | *honeycomb is observed in bottom dome and balcony. | |||||||||||||
| 8 | 20013896 | PIPRIYA BADARKA PWS SVS | 20013896/01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | *honeycomb is observed in OHT pile cap . | |||||||||||||
| 9 | 20016095 | USARA JARWAL PWS | 20016095/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | *Honeycombing is observed in the cylindrical wall of the OHT, with visible voids and stone pockets, indicating poor compaction and inadequate concrete consolidation. | |||||||||||||
| 10 | 20031358 | GODANI BASAHI CHITTAURA PWS | 20031358/01 | No | Yes | No | No | No | No | No | No | No | No | No | No | No | Resolved | *Miss alignment in 1st lift column above 1st brace. | ||||||||||||
| 11 | 20013702 | KHAJURI PAYAGPUR PWS | 20013702/01 | No | No | No | Yes | No | No | No | No | No | No | No | No | No | Resolved | *Staircase steel exposed form several months rusting issue. | ||||||||||||
| 12 | 20014116 | BARAUNWA BHADUALI CHITTAURA PWS | 20014116/01 | Yes | Yes | No | No | Yes | No | No | No | No | No | No | No | No | Resolved | Resolved | Resolved | *Honeycombing is visible at multiple locations in the OHT structure. *Misalignment of column and brace junctions has been observed due to the use of improper shuttering. *Overall workmanship appears to be substandard, with visible seams and defects in the concrete finish. | ||||||||||
| 13 | 20014686 | GAURYA HUZOORPUR PWS | 20014686/01 | No | No | Yes | No | No | No | No | No | No | No | No | No | No | Resolved | *Cube test failed. | ||||||||||||
| 14 | 20092525 | MUSEPATTI PHAKHARPUR PWS | 20092525/01 | No | Yes | No | No | No | No | No | No | No | No | No | No | No | Resolved | *Misalignment and bulging at junction point of column and beam. *Centreline of beam and column are eccentric. | ||||||||||||
| 15 | 20072319 | SEMARI GHATHI MIHIPURWA PWS | 20072319/01 | Yes | Yes | No | Yes | Yes | No | Yes | No | No | No | No | No | No | Resolved | *Honeycombing was found on the column surfaces, which indicates improper compaction and poor workmanship. *Longitudinal reinforcement has not been placed as per the design specifications. *Junction boxes were not provided during the pouring of concrete at column brace. *Cement bags were used to fill the gaps between shuttering instead of approved materials like thermo cool. | ||||||||||||
| 16 | 20016162 | KHAOIRA DHAUKAL SHIVPUR PWS | 20016162/01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | Resolved | *Major Honeycombing is visible at the column and bracing junction due to improper shuttering and poor-quality execution. | ||||||||||||
| 17 | 20020722 | KURSAHA VISESHWARGANJ PWS | 20020722/01 | No | No | No | Yes | No | No | No | No | No | No | No | No | No | Resolved | *The OHT work has been stopped since 10 months after the column constructed up to ground level. Since then the work has been stopped. The re-bars are exposed to rust. | ||||||||||||
| 18 | 20061996 | KATORWA & NETHIYA VISESHWARGANJ MVS PWS | 20061996/01 | No | No | No | Yes | No | No | No | No | No | No | No | No | No | Resolved | *Reinforcement of brace is executed since 8 months ago, but casting is not done till yet due to this steel used in brace got completely corrode. | ||||||||||||
| 19 | 20100759 | LAKHAIYA KALA, LALBOJHI & SISWARA RO MVS PWS | 20100759/01 | Yes | Yes | No | No | Yes | No | Yes | No | No | No | No | No | No | Resolved | Resolved | Resolved | Resolved | *Honeycombing has been observed at various locations in OHT structure, indicating poor concrete compaction during casting. *Verticality issues observed in Columns. *Improper arrangement for curing. *Junction boxes were not provided during the pouring of concrete. Inadequate shuttering has been used at column and brace junction. | |||||||||
| 20 | 20020334 | MOHANPURMAFI & SUMERPUR PAYAGPUR MVS PWS | 20020334/01 | No | No | Yes | No | No | No | No | No | No | No | No | No | No | Resolved | *Cube test failed for the sample of 1st Staircase. | ||||||||||||
| 21 | 20017829 | RAMNAGAR GULHARIYA NAWABGANJ PWS | 20017829/01 | Yes | Yes | No | No | Yes | No | No | No | No | No | No | No | No | Resolved | Resolved | Resolved | *Brace dimension is not as per approved drawing. *Major Honeycombing observed in OHT brace and column junction points. *Column is not vertically align and section is not properly casted. | ||||||||||
| 22 | 20016090 | PURAINA VISESHWARGANJ PWS | 20016090/01 | Yes | Yes | No | Yes | No | No | No | No | No | No | No | No | No | Resolved | Resolved | Resolved | *The OHT work has been stopped for the passed 3 months. Major honeycombing is visible at the column brace junction due to improper shuttering and poor quality execution. *All the exposed steel in the structure has rusted due to prolonged exposure to the environment. *Misalignment in Beams and columns. | ||||||||||
| 23 | 20016166 | JOKAHA VISESHWARGANJ PWS | 20016166/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | *All the exposed steel in the structure has rusted due to prolonged exposure to the environment. | ||||||||||||
| 24 | 20069817 | BALA NAGAR KODARI VISHESHWARGANJ PWS | 20069817/01 | Yes | No | No | Yes | No | No | No | No | No | No | No | No | No | Resolved | Resolved | *Honey comb is observed in column and brace beam. *column steel is exposed from periods of time it lead rusting. | |||||||||||
| 25 | 20016068 | IMALIYAGANJ PAYAGPUR PWS | 20016068/01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | Resolved | *honey comb is observed in column and brace beam Junction | ||||||||||||
| 26 | 20048283 | SHEKHAPUR & BEHARA HUZOORPUR MVS PWS | 20048283/01 | No | No | No | No | Yes | No | Yes | No | No | No | No | No | No | Resolved | Resolved | *Shuttering of brace and column is not removed since 5 months. *Curing is not done as per required. | |||||||||||
| 27 | 20048423 | BANJARIYA BALAHA PWS | 20048423/01 | Yes | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | Resolved | *honeycomb is observed in stair case, column and brace beam Junction *no arrangement of proper curing of structure. | |||||||||||
| 28 | 20072233 | GANDARA JARWAL PWS | 20072233/01 | No | No | No | No | Yes | No | No | No | No | No | No | No | No | Resolved | *Steel reinforcement is not executed as required lapping and hooks in ring is not properly provided. | ||||||||||||
| 29 | 20013700 | DERWA HARBANSPUR PAYAGPUR PWS | 20013700/01 | Yes | No | No | No | Yes | No | No | No | No | No | No | No | No | Resolved | Resolved | *honey comb observed at various places in structure. *material quality used is not as per standard. | |||||||||||
| 30 | 20039630 | JIGANIYA CHHATRAPAL SINGH HUZOORPUR PWS | 20039630/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | *poor finishing observed at the surface of structure minor honey comb and surface cracks seams at the structure | ||||||||||||
| 31 | 20013881 | SHAHPUR KALAN BALAHA PWS | 20013881/01 | Yes | No | No | No | Yes | No | No | No | No | No | No | No | No | Resolved | Resolved | *Honey comb observed at various places in structure. *cracks observed in between the stair case flight and cantilever beam. | |||||||||||
| 32 | 20085904 | KANCHHAR & SULTANA MAFI VISESWARGANJ MVS PWS | 20085904/01 | No | No | No | Yes | No | No | Yes | No | No | No | No | No | No | Resolved | Resolved | *Due to prolonged suspension of work , all reinforcement steel in the column of the OHT structure has become rusted from continuous exposure without any protective covering . *some vertical bars is cut from column. | |||||||||||
| 33 | 20014101 | JHALA TARAHAR PAYAGPUR PWS | 20014101/01 | No | No | No | Yes | No | No | Yes | No | No | No | No | No | No | Resolved | Resolved | *Rusted steel is using the construction of OHT Pile cap work. *Un approved material is dumped at site. | |||||||||||
| 34 | 20014715 | TULA MAJHAUWA RISIYA MVS PWS | 20014715/01 | No | No | No | No | Yes | No | Yes | No | No | No | No | No | No | Resolved | Resolved | *Dimensional error in the brace beam not as per approved drg. *Shuttering of stair is not removed since last year and curing for the same is not doe as required. | |||||||||||
| 35 | 20016197 | BISWA PHAKHARPUR MVS PWS | 20016197/01 | No | No | No | Yes | Yes | No | Yes | No | No | No | No | No | No | Resolved | Resolved | Resolved | *dimensional error found is stair case work not as per approved drg. *stacking of material at site is very poor, all the steel dumped at site is in open area it may leads rusting. | ||||||||||
| 36 | 20077218 | RAJAPUR KHURD & SASNA PHAKHARPUR MVS PWS | 20077218/01 | No | No | No | No | Yes | No | No | No | No | No | No | No | No | Resolved | *one side of OHT stair case got titled due to improper shuttering. | ||||||||||||
| 37 | 20020700 | SAHJANA NAWABGANJ PWS | 20020700/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | *the reinforcement above column is cut and theft. | ||||||||||||
| 38 | 20072358 | KALUYEE PAYAGPUR PWS | 20072358/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | *The column at the OHT GL level exhibited rusted steel and bend steel. | ||||||||||||
| 39 | 20077184 | SARRAKALA MIHIPURWA MVS PWS | 20077184/01 | No | No | Yes | No | No | No | No | No | No | No | No | No | No | Resolved | *OHT 1st lift column 28 days cube not attain desired strength. | ||||||||||||
| 40 | 20072258 | KANDAULI KAISARGANJ PWS | 20072258/01 | No | No | Yes | No | No | No | No | No | No | No | No | No | No | Resolved | *OHt 5th flight 28 days cube not attain desired strength. | ||||||||||||
| 41 | 20035173 | PARASPUR WATER SUPPLY SCHEME | 20035173/01 | No | No | No | No | Yes | No | No | No | No | No | No | No | No | Resolved | *due to poor workman ship Brace beam (tie beam) is observed to be projecting inward from the column face | ||||||||||||
| 42 | 20020344 | ROHNI BHARI PAYAGPUR PWS | 20020344/01 | No | No | No | Yes | No | No | No | No | No | No | No | No | No | Resolved | *reinforcement rusting issue. | ||||||||||||
| 43 | 20076876 | VISAINDHA KAISERGANJ MVS PWS | 20076876/01 | No | No | Yes | No | No | No | No | No | No | No | No | No | No | Resolved | *28 days cube fail of bottom dome. | ||||||||||||
| 44 | 20039658 | KAREHANA MAHASI PWS | 20039658/01 | No | No | No | No | Yes | No | No | No | No | No | No | No | No | Resolved | *surface cracks and improper finishing at staircase. | ||||||||||||
| 45 | 20072368 | ALIPURDARAUNA PHAKARPUR PWS | 20072368/01 | No | No | No | No | Yes | No | No | No | No | No | No | No | No | Resolved | *deviation in staircase execution work not done as per approved drawing. | ||||||||||||
| 46 | 20034905 | KANJARWA MIHIPURWA GRAM PANCHAYAT WATER SCHEME | 20034905/01 | No | No | No | No | Yes | No | No | No | No | No | No | No | No | Resolved | *leakage is observed in cylindrical wall 2nd lift and 3rd lift due to improper compaction. | ||||||||||||
| 47 | 20072189 | AHATA JARWAL PWS | 20072189/01 | No | No | Yes | No | No | No | No | No | No | No | No | No | No | Resolved | *7 DAYS 3rd Lift Cylindrical Wall Cube failed. | ||||||||||||
| 48 | 20048286 | ATHAISHA JARWAL MVS PWS | 20048286/01 | No | No | Yes | No | No | No | No | No | No | No | No | No | No | Resolved | *7 DAYS 2nd Lift Staircase Cube failed. | ||||||||||||
| 49 | 20077215 | GUJAULI KALA PHAKHARPUR MVS PWS | 20077215/01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | Resolved | *honey comb in stair case slab. | ||||||||||||
| 50 | 20072342 | NIDHINAGAR SANKALPA NAWABGANJ PWS | 20072342/01 | No | Yes | No | No | No | No | No | No | No | No | No | No | No | Resolved | *miss alignment in one first brace beam due to improper shuttering | ||||||||||||
| 51 | 20077206 | RUKNAPUR, SAHASRAWA & SATRAHI PAYAGPUR MVS PWS | 20077206/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | *The main reinforcement bar of the OHT (Overhead Tank) column was cut via. Unknown from ground level due to the prolonged stoppage of construction activities. Reinforcement bar has been submerged underwater and cover with mud it can lead to corrosion, which compromises the durability and strength of the structure. | ||||||||||||
| 52 | 20077191 | LALPUR CHANDJHAR & GOPIA MIHIPURWA MVS PWS | 20077191/01 | No | No | No | Yes | No | No | No | No | No | No | No | No | No | Resolved | *RUSTING OF STEEL. | ||||||||||||
| 53 | 20016108 | KALWARI NAWABGANJ PWS | 20016108/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | *OHt column reinforcement is chopped from GL level. | ||||||||||||
| 54 | 20020346 | SAMBHU TEKRI PAYAGPUR PWS | 20020346/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | *Steel is cut from the column at GL level. | ||||||||||||
| 55 | 20018878 | CHAUGOI BILASPUR NAWABGANJ PWS | 20018878/01 | Yes | No | No | Yes | No | No | No | No | No | No | No | No | No | Resolved | *Major honeycomb observed at the column brace junction as well as in the staircase. *Reinforcement in the OHT staircase is exposed after casting of Staircase, indicating poor workmanship. | ||||||||||||
| 56 | 20017524 | CHARDAHA CHANDAN CHITTAURA PWS | 20017524/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | *Reinforcement at GL is deformed. | ||||||||||||
| 57 | 20011160 | RAMWAPUR HUZOORPUR MVS PWS | BAH/PNC/B8/38 | No | No | No | No | Yes | No | No | No | No | No | No | No | No | Resolved | *OHt lightning arrestor Strip is not as provided as required, insulation of strip is not done properly. | ||||||||||||
| 58 | 20016167 | KHANPUR MALLOH VISESHWARGANJ PWS | 20016167/01 | No | No | No | No | Yes | No | Yes | No | No | No | No | No | No | Resolved | *Improper shuttering is used; improper finishing is observed. *Edge and corners of steps is improper, poor finishing seams in staircase. | ||||||||||||
| 59 | 20051979 | NATHUWAPUR MAHASI PWS | 20051979/01 | No | No | No | No | Yes | No | No | No | No | No | No | No | No | *Staircase dimension error riser and thread is not found as required or as per approved drawing. | |||||||||||||
| 60 | 20020191 | MASUDNAGAR BASTHANWA SHIVPUR PWS | 20020191/01 | No | No | No | No | No | No | No | No | No | No | No | No | No | *Deviation in Zinc Alum Tank Installation. | |||||||||||||
| 61 | 20048334 | PEDWA JARWAL MVS PWS | 20048334/01 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | *Deviation in zinc alum erection work at OHT. | |||||||||||||
| 62 | 20020332 | HATWA HARDAS PAYAGPUR MVS PWS | 20020332/01 | No | No | No | No | Yes | No | No | No | No | No | No | No | No | Resolved | *3rd lift staircase few steps dimension is not as per approved drawing deviation seams in dimension of thread and riser. | ||||||||||||
| 63 | 20016654 | KANDAUSA FHAKHARPUR PWS | 20016654/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | *Few vertical column steels chopped at GL level . | ||||||||||||
| 64 | 20013703 | NARAYANPUR PAYAGPUR PWS | 20013703/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | *Few vertical column steels chopped at GL level. | ||||||||||||
| 65 | 20072325 | KATGHAR MIHIPURWA PWS | 20072325/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | *Reinforcement bars at the site have been found cut/chopped by unknown persons/villagers. | ||||||||||||
| 66 | 20072218 | KHANPUR HUZOORPUR PWS | 20072218/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | *Few vertical columns steel chopped at GL level . | ||||||||||||
| 67 | 20072262 | SANTHA KAISARGANJ PWS | 20072262/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | *Few vertical columns steel chopped at GL level . | ||||||||||||
| 68 | 20018877 | BANKURI NAWABGANJ PWS | 20018877/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | *Few vertical column steel chopped at GL level. | ||||||||||||
| 69 | 20072386 | RAMPUR BARAIE RISIA PWS | 20072386/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | *OHT vertical column steel is chopped from GL level . | ||||||||||||
| 70 | 20039633 | PARSOHAR JARWAL PWS | 20039633/01 | Yes | Yes | No | Yes | No | No | No | No | No | No | No | No | No | Resolved | Resolved | Resolved | *Regarding poor finishing of OHT column. *Honeycomb in bottom dome. *Reinforcement steel found exposed. | ||||||||||
| 71 | 20048313 | JUMERPUR JARWAL MVS PWS | 20048313/01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | Resolved | *Honeycomb at OHT column. | ||||||||||||
| 72 | 20072326 | SUJAULI MIHIPURWA PWS | 20072326/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | *Few vertical column steel chopped at GL level . | ||||||||||||
| 73 | 20020240 | DIGIT PURWA VISESHWARGANJ PWS | 20020240/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | *Column reinforcement chopped from GL level of OHT. | ||||||||||||
| 74 | 20034898 | GANGA JUMNI GRAM PANCHAYAT WATER SCHEME | 20034898/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | *Reinforcement bars of column is chopped at GL level. | ||||||||||||
| 75 | 20016089 | JUDA SHIVPUR PWS | 20016089/01 | No | No | No | No | Yes | No | No | No | No | No | No | No | No | Resolved | *Dimensional error in staircase. | ||||||||||||
| 76 | 20059445 | KATGHARA KALA HUZOORPUR MVS PWS | 20059445/01 | No | No | No | No | Yes | No | No | No | No | No | No | No | No | Resolved | *Dimensional error in staircase of OHT. | ||||||||||||
| 77 | 20034885 | DALJIT PURWA GRAM PANCHAYAT WATER SCHEME | 20034885/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | *Vertical column reinforcement is cut from GL level. | ||||||||||||
| 78 | 20075342 | BARKHURDWARAPUR KAISARGANJ MVS PWS | 20075342/01 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | Resolved | *Deviation in Zinc Alum tank installation. | ||||||||||||
| 79 | 20076871 | METAURA & MUSEPUR KAISARGANJ MVS PWS | 20076871/01 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | Resolved | *Deviation in Zinc Alum Tank Installation. | ||||||||||||
| 80 | 20016148 | SAUGAHANA PHAKHARPUR PWS | 20016148/01 | No | Yes | No | No | Yes | No | Yes | No | No | No | No | No | No | Resolved | Resolved | Resolved | *The OHT has not been constructed with proper vertical alignment. *Budling and misalignment at Junction point. *The overall quality of workmanship appears to be below acceptable standards, with visible seams and other inconsistencies. | ||||||||||
| 81 | 20034904 | KAILASHPUR JHOMAN GAON GRAM PANCHAYAT WATER SCHEME | 20034904/01 | No | No | No | No | Yes | No | No | No | No | No | No | No | No | Resolved | *Deviation from drawing in staircase thread and riser. | ||||||||||||
| 82 | 20014113 | SEMRIYAWAN PAYAGPUR PWS | 20014113/01 | No | No | No | No | Yes | No | No | No | No | No | No | No | No | Resolved | *The brace beam dimensions of the 2nd brace were measured and found to be 20-30 mm more than the dimensions specified in the approved drawings. | ||||||||||||
| 83 | 20072266 | SAHWAPUR PACHLAKHI KAISARGANJ PWS | 20072266/01 | No | No | No | No | No | Yes | No | No | No | No | No | No | No | Resolved | *Deviation in Zinc Alum Tank Installation. | ||||||||||||
| 84 | 20014081 | CHAUDHARI GAON MIHIPURWA PWS | 20014081/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | *Leakage and seepage are observed in bottom dome and cylindrical wall. | ||||||||||||
| 85 | 20016202 | NEJABHAR VISESHWARGANJ PWS | 20016202/01 | No | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | *Few vertical columns steel chopped at GL level . | ||||||||||||
| 86 | 20034869 | ARAI KALA GRAM PANCHAYAT WATER SCHEME | 20034869/01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | Resolved | *Honeycomb is observed in 1st brace beam, at few places air voids observed. | ||||||||||||
| 87 | 20018638 | NARAUNDA JARWAL PWS | 20018638/01 | No | No | No | No | Yes | No | No | No | No | No | No | No | No | Resolved | *Poor workman ship seams in the construction of OHT at staircase, air voids and improper finishing seams. | ||||||||||||
| 88 | 20069803 | MAKRANDPUR MAHIS PWS | 20069803/01 | No | No | No | No | Yes | No | No | No | No | No | No | No | No | Resolved | *Regarding poor workmanship, column starter constructed in ir regular shape. | ||||||||||||
| 89 | 8362941 | RAY DEEH GRAM PANCHAYAT RURAL DRINKING WATER SUPPLY SCHEME | 8362941/01 | Yes | No | No | No | No | No | No | No | No | No | No | No | No | Resolved | *Honeycomb in staircase 7th lift. | ||||||||||||