| S.No. | Scheme ID | Scheme Name | OHT Code | Non-Compliance | Compliance(Current Status) | Description
|
||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Major Honey Comb | Alignment | Cube Test | Exposure | Deviation | Tank Observation | Other | SBC Issue | Demolish Partially | Demolish Fully | Under Examination | Serious Observation | Water Body | Compliance Major Honey Comb | Compliance Alignment | Compliance Cube Test | Compliance Exposure | Compliance Deviation | Compliance Tank | Compliance Other | Compliance SBC Issue | Compliance Demolish Partially | Compliance Demolish Fully | Compliance Under Examination | Compliance Serious Observation | Compliance Water Body | |||||
| 1 | 8152383 | Dhawarra GOV | OHT / 004 / NAGARA DANG | Yes | Yes | No | No | No | No | No | No | No | No | No | No | No | 1. Major honeycomb and reinforcement is exposed in Tie beam, ring beam & bottom dome. 2. Deviation in Verticality of column alignment has been observed. | |||||||||||||
| 2 | 8152383 | Dhawarra GOV | OHT / 030 / SAITHWARA | Yes | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | Resolved | 1. Major honeycomb and reinforcement are exposed in cylindrical wall, ring beam of bottom dome and top dome. 2. Leakage is observed from the container wall and bottom dome of OHT. | |||||||||||
| 3 | 8152383 | Dhawarra GOV | OHT / 005 / BUDHWARA | Yes | Yes | No | No | No | No | Yes | No | No | No | No | No | No | 1. Major honeycombing and exposed steel has been observed in most of the OHT concrete work including ring beam and bottom dome. 2. Verticality of column alignment is observed which is indicating poor compaction and workmanship. 3. Voids has been observed between the conical wall and ring beam of tank. | |||||||||||||
| 4 | 8152383 | Dhawarra GOV | OHT / 017 / ARI | Yes | Yes | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | 1. Major honeycombing and reinforcement are exposed from the bottom dome & ring beam of OHT. 2. Misalignment has been observed in the OHT columns. 3. Leakage is observed from cylindrical wall and bottom dome of OHT. (Sr. No. 3 Closed) | ||||||||||||
| 5 | 8152383 | Dhawarra GOV | OHT / 025 / NARWARA | Yes | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | 1. Major honeycombing and exposed steel has been observed in most of the OHT concrete work including OHT columns and bottom dome. 2. Continues leakage and seepage is observed at the bottom dome. (Closed Sr. No. 2) | ||||||||||||
| 6 | 8152383 | Dhawarra GOV | OHT / 019 / SWASA MAF | No | Yes | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | 1. Deviation in verticality of columns indicating poor compaction and workmanship. 2. The Leakage has been observed from OHT container. (Closed Sr. No. 2) | ||||||||||||
| 7 | 8152383 | Dhawarra GOV | OHT / 013 / BHANDARA | Yes | No | No | No | No | No | No | No | No | No | No | No | No | Major honeycombing and exposed steel has been observed in certain parts of Overhead Tank (OHT). | |||||||||||||
| 8 | 8152383 | Dhawarra GOV | OHT / 016 /MUDHARI | Yes | Yes | No | Yes | No | No | No | No | No | No | No | No | No | 1• Major honeycombing has been observed in certain parts of Overhead Tank (OHT). 2• Misalignment has been observed in the OHT columns. 3• Reinforcement is exposed from the certain parts of OHT. | |||||||||||||
| 9 | 8152383 | Dhawarra GOV | OHT / 026 / TIKARIYA PANWARI | Yes | Yes | No | Yes | No | No | No | No | No | No | No | No | No | 1• Major honeycombing has been observed in certain parts of Overhead Tank (OHT). 2• Misalignment has been observed in the OHT columns. 3• Reinforcement is exposed from the certain parts of OHT. | |||||||||||||
| 10 | 8152383 | Dhawarra GOV | OHT / 008 / DIKWAHA | Yes | No | No | Yes | No | No | No | No | No | No | No | No | No | Resolved | Resolved | ||||||||||||
| 11 | 8152383 | Dhawarra GOV | OHT / 007 / BASORA | Yes | Yes | No | Yes | No | No | No | No | No | No | No | No | No | Resolved | 1• Major honeycombing has been observed in 3rd, 4th brace, Main ring beam, significant Exposed steel and honeycomb conical wall and balcony of Overhead Tank (OHT), indicating poor compaction and workmanship, with significant leakages at bottom dome. 2• Misalignment in columns of tanks and staircase has been observed in the OHT. 3• Reinforcement is exposed at 4th tie beam of staircase and 3rd and 4th Landing of staircase bottom dome near inlet pipe, main ring beam. | ||||||||||||
| 12 | 8152383 | Dhawarra GOV | OHT / 023 /DHUDHAIYA | Yes | Yes | No | Yes | No | No | No | No | No | No | No | No | No | Resolved | Leakage rectification has been done. | ||||||||||||
| 13 | 8152383 | Dhawarra GOV | OHT / 014 / ATRAR MAF | Yes | Yes | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | Resolved | Leakage rectificaiton has been done. | |||||||||||
| 14 | 8152383 | Dhawarra GOV | OHT / 015 / DIGARIYA | Yes | Yes | No | Yes | No | No | No | No | No | No | No | No | No | Resolved | Resolved | ||||||||||||
| 15 | 8152383 | Dhawarra GOV | OHT / 021 / RAHELIA | Yes | Yes | No | No | No | No | No | No | No | No | No | No | No | Resolved | Resolved | ||||||||||||
| 16 | 8152383 | Dhawarra GOV | OHT / 006 / TOLA SOYAM | Yes | Yes | No | No | Yes | No | Yes | No | No | No | No | No | No | Resolved | Resolved | 1.• Major honeycombing has been observed in certain parts of Overhead Tank (OHT). 2• The diameter of columns in the OHT is not uniform across the OHT. 3• Deviation in verticality of columns indicating poor compaction and workmanship.- Closed Drawing submitted. 4• Concrete quality in the OHT is not proper as per the visual inspection carried out. 5• Voids has been observed in the junctions points of beam and column of OHT. | |||||||||||
| 17 | 8152383 | Dhawarra GOV | OHT / 012 / LEVA | Yes | Yes | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | 1• Major honeycombing has been observed in certain parts of Overhead Tank (OHT). 2• Misalignment has been observed in the OHT columns. 3• Cracks observed at junction point of column and beam. 4• The Leakage has been observed from OHT. | ||||||||||||
| 18 | 8152383 | Dhawarra GOV | OHT / 029 / KAR PAHARIYA | No | No | No | Yes | No | No | Yes | No | No | No | No | No | No | Resolved | Resolved | ||||||||||||
| 19 | 8152383 | Dhawarra GOV | OHT / 003 / LUHEDI | Yes | No | No | No | No | No | No | No | No | No | No | No | No | ||||||||||||||
| 20 | 8152383 | Dhawarra GOV | OHT / 022 / PACH PAHARA | Yes | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | |||||||||||||
| 21 | 8152383 | Dhawarra GOV | OHT / 027 / CHITTARWARA | Yes | No | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | 1. Major honeycombing and exposed steel has been observed in the ring beam, columns and slab of Overhead Tank (OHT). 2. Leakage has been observed from the bottom dome of tank. (Closed) 3. Voids and exposed steel is observed in the junction point of beam and column of OHT. 4. Crack has been observed in the OHT columns. | ||||||||||||
| 22 | 8152383 | Dhawarra GOV | OHT / 018 / KAITHUARA | Yes | Yes | No | Yes | No | No | No | No | No | No | No | No | No | Major honeycombing & reinforcement is exposed from the OHT slab. | |||||||||||||
| 23 | 8152383 | Dhawarra GOV | OHT / 011 / MAHUA BANDH | Yes | Yes | No | Yes | No | No | Yes | No | No | No | No | No | No | Resolved | Resolved | 1. Major honeycombing has been observed in certain parts of Overhead Tank (OHT). 2. Misalignment has been observed in the OHT columns.- Resolved and cheacked by TS 3. Reinforcement is exposed from the certain parts of OHT. 4. Cracks observed at junction point of column and beam. | |||||||||||
| 24 | 8152383 | Dhawarra GOV | ESR-01 | Yes | Yes | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | 1. Major honeycombing and exposed steel has been observed in balcony near staircase, 5th outer brace and on main ring beam Overhead Tank (OHT). 2. Verticality of column alignment is observed which is indicating poor compaction and workmanship. 3. Cracks has been observed in the junction point of beam and column. 4. Voids has been observed in the conical wall of tank. 5. Leakages spotted has been found in the container wall & bottom dome. | ||||||||||||
| 25 | 8152383 | Dhawarra GOV | OHT / 009 / BILKHI | Yes | Yes | No | Yes | No | No | No | No | No | No | No | No | No | Resolved | Resolved | Resolved | |||||||||||
| 26 | 8152383 | Dhawarra GOV | OHT / 010 / DHAWARRA | Yes | Yes | No | No | No | No | Yes | No | No | No | No | No | No | Resolved | 1. Major honeycombing and exposed steel has been observed in most of the OHT concrete work including OHT beams and bottom dome. 2. Leakage has been observed in the OHT. 3. Deviation in verticality of columns indicating poor compaction and workmanship. | ||||||||||||