Agency-wise Major/critical Ncs at OHT

S.No. Scheme ID Scheme Name OHT Code Non-Compliance Compliance(Current Status)
Description
Major Honey Comb Alignment Cube Test Exposure Deviation Tank Observation Other SBC Issue Demolish Partially Demolish Fully Under Examination Serious Observation Water Body Compliance Major Honey Comb Compliance Alignment Compliance Cube Test Compliance Exposure Compliance Deviation Compliance Tank Compliance Other Compliance SBC Issue Compliance Demolish Partially Compliance Demolish Fully Compliance Under Examination Compliance Serious Observation Compliance Water Body
1 20084470 Athlohia GP WSS 20084470-01 No No No No No No No No No No No No No
2 20085121 Parsa Jhakariya GP WSS 20085121-01 No No No No No No Yes No No No No No No Resolved
3 20084470 Athlohia GP WSS 20084470/01 Yes No No No No No No No No No No No No Resolved OHT Raft demolished and reconstruct.
4 20089956 CHANDIDEEHA GRAM PANCHAYAT WATER SUPPLY SCHEME 20089956-01 No No No No No No Yes No No No No No No Resolved 7 days and 28 days cube test result found ok.
5 20084318 NAUDAND GP WSS 20084318-01 No No Yes No No No No No No No No No No Resolved NDT done and found ok value found 34 N/mm2S
6 20083192 PRATPPUR & MAHLA GOV WSS 20083192-01 No No No No Yes No No No No No No No No
7 20083192 PRATPPUR & MAHLA GOV WSS 20083192/01 No No No No No No No No No No No No No
8 20082654 BHAGAUSA GP WSS 20082654-01 No No No No Yes No No No No No No No No Resolved Column steel Lap shall be provided only in the center half of clear column height, and not within a joint or within a distance of 2D from face of the beam.